Alarm "No HW Time":
After a boot procedure, an inconsistent time was established in the hardware module. The clock then
initializes itself with a starting value and does not have correct time until the next synchronization.
The loss of the hardware time does not come about until after approx. 2 weeks without power supply.
Alarm „sync. protected":
In the synchronisation mode „protected" the time of the input signal changed more than 5s. The synchro-
nization is ignored and this message is generated. Check the correct function and parameterization of
the used input anyway. This alarm can not be quitted. In parameter 221/3A curr. time diff. The current
time difference to the input is shown. If this shall be accepted, the parameter 218/3A mode has to set
to the value „jump" or „step" to take over the new input time. After that the parameter should be reset to
the value „protected".
Warning „time deviation":
The external time deviates from the internal time. During normal operation this indicates an inconsisten-
cy of the external synchronization.
see also "Protected synchronization", page 23.
Alarm „time set":
The time has been set by the external synchronization. During normal operation this indicates an incon-
sistency of the external synchronization.
see also "Protected synchronization", page 23.
Further Warnings:
•
"EE Updt Pg0", "EE Updt Pg1" new firmware (new parameter structure) is recognized.
•
"Input val." New parameter value was not validated with
•
"Password missing" Password to increase the access level is missing.
•
"Not poss." Parameter is write-protected (first deactivate Ethernet).
If the event of serious internal operating errors, further messages appear and such cases must be re-
ported to the Service Dept.
Order No. 2XV9450-1AR53-BA
.
Version 2.0
User Manual SICLOCK TS V2.0