13.5 Technical data
Inputs
Outputs
Alarm relay
LAN connection
Interfaces
Output voltage
Supply voltage
Power consumption
Fuses
Precision
Precision
Power reserve
Surrounding tempe-
rature
Protection class
(acc. to IEC529)
Dimensions
Installation
Weight
Table 14 Technical Data
42
1 TTY 20mA (telegrams, DCF77)
active/passive insulated
1 TTY 40 mA (GPS1000)
1 RS422 (telegrams, IRIG-A003,B003)
IRIG-A133,B123
1 TTY 20 mA active/passive, 24V
1 TTY 20 mA active, 24V
1 RS422
IRIG-A133,B123
Change-over contact DC: 150V/1A 30W
AC: 125V/1A 60VA
AUI 10BASE5
10BASE-T
RS232 PC interface
24V/0,5A insulated
24V...110V DC +10%, -20%
or
DC: 90V...250V DC +10%, -20%
AC: 90V...230V AC +10%, -20% 50/60Hz
approx. 60 W, 180W when switched on
10 A neutral
internal clock
IRIG
internal clock
0...50 °C
IP 20
dimensions (W x H x D)
35mm DIN rail
Version 2.0
Terminal block X2, pins 5-8
Terminal block X2, pins 9, 10
Terminal block X2, pins 15, 16
BNC bush X7
Terminal block X2, pins 1-4
Terminal block X2, pins 13,14
Terminal block X2, pins 17, 18
BNC bush X8
Terminal block X2, pins 11, 21,
22
15-pol. SUBD bush X5
RJ45 bush X6
15-pol. SUBD bush X5 (ITP)
9-pol. SUBD bush X3
Terminal block X2, Pin 19, 12
3-pol. Terminal block X1
50 ppm at 25°C free running
0,07...1ppm depending on syn-
chronization
1ms
>14 days buffered without batte-
ries
250 x 135 x 142mm
DIN rail EN 50022-35 (15mm
high)
or SIMATIC S5 norm profile
6ES5 710-8Maxx
3,2 kg
Order No. 2XV9450AR53-BA