Maintenance
The FMR is to a large extent maintenance-free when used as intended.
ATTENTION!
If the exterior becomes soiled, FMR should be cleaned only with compatible cleaning agents.
In case of doubt, make a test of compatibility.
Error and malfunctions of the FMR
General error messages
(shown only with external setpoint SETP EXT and activated SIG ERR)
Display
Cause of error
INT.ERROR
Internal error
SP FAULT
Signal error, setpoint
Process controller
P1 FAULT
Signal error, actual value P1
Flow Control System
P2 FAULT
Signal error, actual value P2
Flow Control System
TMP FAULT
Signal error, actual value, temperature
Flow Control System
Error messages on execution of the function X.TUNE (AUTOTUNE)
Display
Cause of error
X.ERR 1
No compressed air connected
X.ERR 2
Compressed air failure during
AUTOTUNE
X.ERR 3
Exhaust side of actuator or positioning
system leaky
X.ERR 4
Pressurizing side of positioning system
leaky
X.ERR 6
The end positions for POS-MIN and
POS-MAX lie too close together
X.ERR 7
False allocation of POS-MIN and POS-
MAX
Error message on execution of the function P.Q'LIN
Display
Cause of error
Q.ERR 1
No pressure supply connected
No change in process variable
Q.ERR 2
Current curve point of the valve stroke
not reached, since
• supply pressure failure during
P.Q 'LIN or
• no AUTOTUNE has been executed
24 - 8750
Make sure that the FMR does not come into contact with aggressive
media.
Remedy
not possible, device faulty
check signal
check signal
check signal
check signal
Remedy
Connect compressed air
Check compressed air supply
not possible, device faulty
not possible, device faulty
Check whether the allocation of the end
positions to POS-MIN and POS-MAX via
function TUNE-POS is correct.
If incorrect: repeat execution of TUNE-
POS.
If correct: TUNE-POS with this allocation of
end positions is impossible, they lie too
close together.
To determine POS-MIN and POS-MAX,
drive the actuator in each case in the
direction shown on the display.
Remedy
Connect pressure supply
Check process, if applicable, switch on
pump or open shut-off valve
• Check supply pressure
• Execute AUTOTUNE