Commissioning
The most important codes for commissioning
Code
No.
Name
C0002
Saving of own
*
settings
s
uSEr
(cont.)
C0002
Loading/copyin
*
g of your own
s
basic settings
uSEr
(cont.)
C0003
Non−volatile
*
parameter
v
saving
112
efesotomasyon.com - Lenze
Possible settings
Lenze
Selection
ð
9
PAR1
5
Own settings
6
Own settings
7
Own settings
8
Own settings
1
0
Parameter not saved in EEPROM
1
Parameter always saved in
EEPROM
3
Own settings saved in EEPROM
EDK82MV371 DE/EN/FR 6.0
Own settings
ð
PAR1
ð
PAR2
ð
PAR3
ð
PAR4
IMPORTANT
You can save your own basic
settings for a controller (e.g.
machine delivery status):
1. Ensure that parameter
set 1 is active
2. Controller inhibit
3. Set C0003 = 3,
acknowledge with v
4. Set C0002 = 9,
acknowledge with v,
to save your own basic
settings
5. Set C0003 = 1,
acknowledge with v
6. Enable the controller.
Using this function, PAR1
can be copied to parameter
sets PAR2 ... PAR4
Restorage of own basic
setting in the selected
parameter set
Data loss after mains
disconnection
Active after every mains
l
connection
l
Cyclic parameter changes
via bus module are not
allowed.
The parameter set 1 saved
as own basic setting with
C0002 = 9
L