Herunterladen Inhalt Inhalt Diese Seite drucken

Using The Device; Automatic Reset - Eaton EMT6-K Handbuch

Vorschau ausblenden Andere Handbücher für EMT6-K:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4 Using the device

4.1 Automatic reset

4 Using the device
4.1 Automatic reset
52
The EMT6, EMT62, EMT6-K and EMT6(230V) devices have a setting fixed to
"Automatic reset" mode. The automatic reset can also be selected with the
EMT6-DB, EMT6-DB(230V), EMT6-KDB and EMT6-DBK. The selector switch
(→ Figure 6, page 49, legend ⑤ ) is set to AUTO for this purpose.
EMT6...
A1/A2
3600 Ω
T1/T2
1600 Ω
0 Ω
13
14
21
22
13
14
21
22
Tripped LED
Figure 8: Function diagram "automatic reset" with the EMT6...
EMT62...
A1/A2
3600 Ω
1T1/T2
1600 Ω
0 Ω
3600 Ω
2T1/T2
11600 Ω
0 Ω
13
14
13
14
23
24
23
24
Trip LED 1
Trip LED 2
Figure 9: Function diagram "automatic reset" with the EMT62...
After it has tripped, the device is reset when the equipment has cooled
down.
The sensor circuits of the EMT6-K, EMT6-KDB and EMT6-DBK have
additional short-circuit monitoring in the sensor circuit (→ Figure 10, page
53).
EMT6 10/16 MN03407006Z-DE/EN www.eaton.com