The following operating modes can be selected by means of wiring the pump differently:
A
Temperature select screw
B
Time switch with switching increments
C
Function selector
To disable DHW circulation manually,
set function switch (C) to OFF.
Time-independent DHW circulation - Wiring Option A
In this mode, the DHW circulation pump is enabled by
briefly operating the hot water draw-off point and is shut
off by the built-in anti-scaling thermostat when the
preset DHW circulation return temperature is reached.
The time switch is not used with this mode (to avoid
continuous operation).
Set function selector (C) to ON.
1
Power supply (230 V - 50 Hz)
2
Flow switch (FLS)
3
Freshwater module primary pump (HT pump)
4
HE pump PWM signal
5
DHW circulation unit (CIRC PUMP)
Time-dependent DHW circulation - Wiring Option B
The DHW circulation pump is started by a separately
adjustable time switch. DHW circulation stops when the
preset DHW circulation return temperature is reached.
The pump cycling operation is thermostat-driven. DHW
circulation is disabled outside of the preset periods.
Set function selector (C) to TIMER.