4.14

Information regarding UL

HINWEIS
Das folgende Kapitel wird unabhängig von der Sprache dieser Dokumentation auf-
grund von UL-Anforderungen immer in englischer Sprache abgedruckt.
4.14.1

Field Wiring Power Terminals

MDP90A-...-
0100 (size 1)
X1
0100 (size 1A)
X1
0250
X1
MDA90A-...-
0020 – 0120
X2
0160 – 0240
X2
0320 – 0480
X2
MDD90A-...-
0020 – 0040
X2
0020 – 0080
X2
X4
4.14.2

Short Circuit Current Rating

Suitable for use on a circuit capable of delivering not more than
Max. voltage is limited to 500 V.
Use 60/75 °C solid or stranded copper wire only sized at 14 AWG minimum. Suita-
ble for 1 wire per terminal.
For double-axis modules use wire size 12 - 14 AWG
Tighten terminals to in-lbs (Nm) as follows
Tightening torque in-lbs (Nm)
Line connection
4.4254 – 5.3105 (0.5 – 0.6)
4.4254 – 5.3105 (0.5 – 0.6)
23.552 – 35.403 (3.0 – 4.0)
Motor connection
4.4254 – 5.3105 (0.5 – 0.6)
13.276 – 15.046 (1.5 – 1.7)
23.552 – 35.403 (3.0 – 4.0
Motor connection
4.4254 – 5.3105 (0.5 – 0.6)
13.276 – 15.046 (1.5 – 1.7)
DC link connection
23.552 – 35.403 (3.0 – 4.0
5000 rms symmetrical amperes when protected by fuses and circuit breakers as
described in the tables below.
1800 rms symmetrical amperes when protected by fuses, circuit breakers and Ty-
pe E Combination Motor Controllers as described in the tables below.
Power supply module
Braking resistor terminals
X3
4.4254 – 5.3105 (0.5 – 0.6)
X3
4.4254 – 5.3105 (0.5 – 0.6)
X3
23.552 – 35.403 (3.0 – 4.0)
Single-axis module
-
-
-
Double-axis module
-
-
All modules
23.552 – 35.403 (3.0 – 4.0
Betriebsanleitung – MOVIDRIVE
Installation
Information regarding UL
-
-
-
-
-
-
-
PE connection
®
modular
4