Herunterladen Inhalt Inhalt Diese Seite drucken

PeakTech 2695 Bedienungsanleitung Seite 13

Digitaler isolationstester/ insulation tester
Vorschau ausblenden Andere Handbücher für 2695:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Meg Ohms
Terminal
Voltage
(open circuit
voltage)
125V
0.125~4.000 MΩ
(0%~+10%)
4.001~40.00 MΩ
40.01~400.0 MΩ
400.1~4000 MΩ
250 V
0.250~4.000 MΩ
(0%~+10%)
4.001~40.00 MΩ
40.01~400.0 MΩ
400.1~4000 MΩ
500 V
0.500~4.000 MΩ
(0%~+10%)
4.001~40.00 MΩ
40.01~400.0 MΩ
400.1~4000 MΩ
1000 V
1.000~4.000 MΩ
(0%~+10%)
4.001~40.00 M
40.01~400.0 M
400.1~4000
Reso-
Range
lution
0.001 MΩ
0.01 MΩ
0.1
1
0.001 MΩ
0.01 MΩ
0.1
1
0.001 MΩ
0.01 MΩ
0.1
1
0.001 MΩ
Ω
0.01
Ω
0.1
Ω
M
1
Accuracy
+(2%+10)
+(2%+10)
+(4%+ 5)
+(5%+ 5)
+(2%+10)
+(2%+10)
+(3%+ 5)
+(4%+ 5)
+(2%+10)
+(2%+10)
+(2%+ 5)
+(4%+ 5)
+(3%+10)
Ω
+(2%+ 10)
M
Ω
+(2%+ 5)
M
Ω
+(4%+ 5)
M
-12-
Test Current
1 mA (+ 10%) @
load 125kΩ
1 mA (+ 10%) @
load 250kΩ
1 mA (+ 10%) @
load 500kΩ
1 mA (+ 10%) @
load 1MΩ
Short
circuit
current
≥1mA
≥1mA
≥1mA
≥1mA