Safety inspection

Safety Inspection
This chapter describes the safety inspection for the inverter described in this service man-
ual. This chapter was produced in accordance with "DIN VDE 0701-0702" and "ÖVE/
ÖNORM E8701-1".
Please also observe the requirements and standards for your particular country, since
there may be deviations in the measured values or inspection steps.
If there are no requirements and standards for your particular country, Fronius recom-
mends that this inspection is still carried out.
The safety inspection must only be conducted on a completely assembled device.

Responsibility

The repairs technician is responsible for the proper performance and documentation of the
safety inspection, and for the correct inspection result. Fronius accepts no liability.
If a defect is identified during the inspection, the safety inspection must be repeated once
the defect has been eliminated.
The following inspection steps must be carried out in the sequence specified. Every in-
spection must be passed before the next inspection can begin. If one of the inspections
cannot be carried out, the inspector must take the decision, and the responsibility and lia-
bility falls to him regarding whether the safety of the device can still be confirmed. This de-
cision must be justified accordingly and included in the inspection log under Notes.
Scope of Applica-
In principle, a safety inspection according to the standard requirements must be carried out
tion
after repair, overhaul or modification.
Qualification of
The safety inspection may only be carried out by a qualified electrician. These are the peo-
the Inspection
ple who, on the basis of their technical training, knowledge, and experience as well as
Personnel
knowledge of the applicable regulations, can assess the assigned tasks and detect and
prevent electrical and other possible dangers.

Documentation

-
-
-
-
The inspection log for the "safety inspection" can be found in the DownloadCenter on Fro-
nius Partnerweb.
The electrician who carried out the inspections is responsible for documenting them
correctly.
All inspections must be documented in an inspection log and archived as per national
requirements. The measured values as well as the inspection equipment used, and
calibration data must be given.
If an individual inspection cannot be carried out, reasons for the inspector's decision
are to be documented.
If the inspection is not passed, then the device in question must be clearly identified
as unsafe and the operator must be informed. The equipment must no longer be op-
erated.