Anhang
A.1 Modbus
Offset
Anzahl
Name
Register
50037
2
DO 0.0 – Grenzwert
50041
2
DO 0.0 – Index
50043
2
DO 0.0 – Pulse pro kWh/kvarh
50045
2
DO 0.0 – Impulslänge
50047
2
Dialogsprache
50049
2
Phasenbezeichner EU/US
50051
2
Konfigurierbarer Zähler Quelle
50053
2
Display Aktualisierungszyklus
50055
2
Display Kontrast
50057
2
Display Helligkeit
50059
2
Display Helligkeit reduziert
50061
2
Helligkeitsdauer
50063
2
Grenzwert 0 ON/OFF
138
Einheit
Format
Wertebereich
–
Unsigned
0 ... 6
long
0 = comb. limit
1 = limit0
2 = limit1
3 = limit2
4 = limit3
5 = limit4
6 = limit5
–
Unsigned
0 ... 3
long
0 = import kWh
1 = export kWh
2 = import kvarh
3 = export kvarh
–
Unsigned
1 ... 4000
long
–
Unsigned
30 ... 500
long
–
Unsigned
0 German
long
1 English
2 Portugese
3 Turkish
4 Spanish
5 Italian
6 Russian
7 French
8 Chinese
9 Polish
–
Unsigned
0 ... 1
long
0 = IEC
1 = US
–
Unsigned
0 ... 8
long
0 = digital input
1 = digital output
2 = comb. limit
3 = limit0
4 = limit1
5 = limit2
6 = limit3
7 = limit4
8 = limit5
–
Unsigned
Byte 0 → 0
long
Byte 1 → 0
Byte 2 → Port 0 ... 11
Byte 3 → Portbit 0 ... 7
–
Unsigned
0 ... 10
long
%
Unsigned
0 ... 3
long
%
Unsigned
0 ... 3
long
min
Unsigned
0 ... 99
long
–
Unsigned
0 ... 1
long
0 = Off
1 = On
Gerätehandbuch, 06/2024, L1V30558543D-01
Zugriff
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
PAC3120 MID und PAC3220 MID