CHOOSING A LOCATION (acc. DIN 14676)
Fig. 2
Bedroom
Children's room
Living room
Kitchen
Boiler/
utility room
Workshop
Bedroom
Childrens
RM at least
- Do not install in environments that are subject to drafts
(e.g. fan, ventilation...) or bathrooms
- Unit is suitable for kitchens, if false alarms due to
steam can be ruled out
- At the highest installation position on the ceiling in the
middle of the room (not on walls )
- Minimum distance of 50 cm from walls, furniture,
lamps
- Monitored area maximum 60 m
height of 6 m
- Distance between two devices maximum 15 m
- Corridor length maximum 7.5 m
- Not onto the ceiling beam for ceiling beams with a
height of >20 cm, but 1 device per intermediate space
up to a maximum of 36 m
- For ceiling beams with a height of <20 cm, a detector
at the centre of the room (also possible on ceiling
beam)
MoAnltg RWM 250_DE_GB_FR_NL_IT_2015_NEU.indd 25
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
Bath
Kitchen
RM
RM
RM
RM
Childrens
Living room
room
room
optimal
RM
2
with maximum ceiling
in surface area
2
- Platforms/galleries <16 m
wide: 1 detector
• over 16 m
- Roof slopes (slopes below 20° are considered flat
ceilings):
RM
> 20°
RM
> 20°
> 20°
In the event of a fire, this device quickly detects the
build-up of smoke and also the associated rise in
temperature in the room. In order to warn you in good
time, it then emits a loud alarm sound. If you decide
that there is no real need to escape the building you
can temporarily deactivate this signal (for approx.
10 minutes), or temporarily disable it before sounding,
by gently pressing the Test/Stop button (Fig. 1, IV). We
recommend that you then provide good ventilation to
the room to prevent the alarm being triggered again.