Herunterladen Inhalt Inhalt Diese Seite drucken

Maintenance And Repair; Battery Replacement - Amprobe ACD-14-PRO Bedienungsanleitung

600 a trms zangenmultimeter mit doppelanzeige
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Frequency Hz
Function
600 V
Accuracy: ± (1.0 % + 5 LSD)
1)
DC-bias, if any, not more than 50% of Sine rms
Voltage Detection (NCV)
Bar-graph
EF-H (High sensitivity)
Indication
Typical Voltage (Tolerance)
-
10 V (5 V to 25 V)
- -
25 V (20 V to 66 V)
- - -
55 V (50 V to 125 V)
- - - -
110 V (90 V to 200 V)
- - - - -
220 V (>180 V)
Indication: bar-graph segments and audible beep tones proportional to the
field strength
Detection frequency: 50/60 Hz
Detection sensor: inside the top side of the stationary jaw

MAINTENANCE AND REPAIR

If the meter fails to operate, check battery, test leads, etc., and replace as
necessary.
Double check the following:
1. Replace the fuse or battery if the meter does not work.
2. Review the operating instructions for possible mistakes in operating
procedure.
Except for the replacement of the battery, repair of the meter should be
performed only by a Factory Authorized Service Center or by other qualified
instrument service personnel.
The front panel and case can be cleaned with a mild solution of detergent
and water. Apply sparingly with a soft cloth and allow to dry completely
before using. Do not use aromatic hydrocarbons, gasoline or chlorinated
solvents for cleaning.

BATTERY REPLACEMENT

When battery voltage drops below the value required for proper operation,
the battery symbol (
W
Warning
To avoid shock, injury, or damage to the meter, disconnect test leads before
opening case.
1)
Sensitivity
50 V
) appears.
16
(Sine rms)
5.00 Hz to 999.9 Hz
EF-L (Low sensitivity)
Typical Voltage (Tolerance)
40 V (32 V to 70 V)
110 V (55 V to 165 V)
220 V (130 V to 265 V)
400 V (250 V to 500 V)
550 V (>430 V)
Range

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Acd-14-pro-eur

Inhaltsverzeichnis