16.1.2 Mounting the cabinet / Installation

The power and signal cabling should be led through the wall into the cabinet. Only use the cable entries
provided for this purpose.
230V~
N PE L1/U
Fig. 20: Cable entry
1.
Lead the 230V mains power cable through the wall and the cable entry provided in the rear of the unit
(see illustration). Fasten it using appropriate devices, e.g. plastic cable straps.
2.
Make sure that the mains and signal cables don't interfere with the rear panel of the cabinet or the
cabinet frame which is mounted on the rear panel.
3.
Signal cables must only be led through the other cable entries.
Danger – Electrical shock !
Remove all power from the panel before carrying out any installation work!
ESD protection
While handling electronic assemblies, the necessary precautions against electrostatic discharge
must be taken.
Protective and functional earth
The PE conductor must be connected to the corresponding terminal at the mains supply. Connect
the FE terminal of the panel's cabinet with the PE rail of the power distributor panel from which the
fire alarm system will be powered.
To prevent short circuits
All connected power and signal lines must be secured using appropriate fasteners, e.g. plastic cable
binders. Make sure the mains cable will not move and touch the signal lines. Remove all power
(mains and battery) from the fire alarm system before any work is carried out. Make sure to lead all
cables complete with their outer sheaths intact into the cabinet. Only remove the insulation from
those sections which are inside the cabinet.