MESS. DISPLAY
DESCRIPTION
Temporary under
E06
voltage error.
Definitive under
E07
voltage error.
Temporary over
E08
voltage error.
Definitive over
E09
voltage error.
Absence of network
E10
power, in memory.
Error of current
E11
coherency.
E12
Memory error.
E13
Configuration error.
E99
Undefined error.
485E
Communication error.
This error condition occurs whenthe voltage is
20% less than thenominal voltage (400V).
This alarm condition closes the J3contact on
the power board for possible external signals
(alarm light, siren, etc.).
This error occurs when the temporary under
voltage condition remains.
This error condition occurs when the voltage
exceeds by 20% the nominal voltage (500V).
This alarm condition closes the J3 contact on
the power board for possible external signals
(alarm light, siren, etc.).
A definitive over voltage error occurs after a
temporary overvoltage error remains.
This condition occurs following a network
absence.
This condition indicates a motor power
absorption error in terms of its running status.
This condition indicates a problem in restoring
the set parameters. Some of the settings can
be lost.
This error occurs when the control board cannot
correctly communicate with the power part. This
alarm condition closes the J3 contact on the
power board for possible external signals (alarm
light, siren, etc.).
This error occurs when an unforeseen error
takes place.
This signal refers to pump units and is indicated
when the devices are not communicating
correctly.
ACTION
Press the button START/STOP or cut the power off and
wait until the LINE Led switches off and after which
restart the system.
If the error occurs again, contact your nearest
assistance centre.
In questa condizione di errore il modulo tenta di
ripristinare il normale funzionamento dopo 1 minuto,
questo procedimento viene ripetuto fino a cinque
volte Premere il pulsante START/STOP oppure togliere
alimentazione ed attendere fino a che il Led LINE si sia
spento dopodiché alimentare nuovamente per riavviare
il sistema.
Nel caso in cui l' e rrore persista contattare l' a ssistenza
tecnica.
Press the START/STOP button or cut off power and wait
until the red Led LINE goes off, then power again to
reset the system.
If the error occurs again, contact your nearest customer
care centre.
Wait for a few minutes. If the signal remains, press
the button START/STOP or cut the power off and wait
until the LINE Led switches off and after which restart
the system.
Press the button START/STOP or cut the power off and
wait until the LINE Led switches off and after which
restart the system.
If the error occurs again, contact your nearest
assistance centre.
Press the button START/STOP or cut the power off and
wait until the LINE Led switches off and afterwhich
restart the system.
If the error occurs again, contact your nearest
assistance centre.
Press the button START/STOP or cut the power off and
wait until the LINE Led switches off and after which
restart the system.
Check the communication cable. If the error occurs
again, contact your nearest customer care centre.
EN