Maintenance
At least once a year, maintenance should be carried out by an authorised specialist company, by a new
inspection sticker and recorded in a control book.
The following checks must be carried out during maintenance:
External inspection of the system components
Check all relevant power supply units
Function test of the connected system components
Note: The green LEDs OK (operation OK) on the housing door of the SHE control panel and in the SHE
manual call points must be lit continuously.
in the SHE control panel and the SHE manual call points.
The error code or pulse sequence provides an indication of the cause of the fault.
are available from power failure, the SHE functions are maintained for at least 72 hours.
14.2
Maintenance work
The maintenance tasks listed here provide a basic overview in dependence of the system components.
System components
SHE control panel
68
Check for dirt, damage, corrosion and fastening.
Testing of all functions, visual inspection of the function and fault displays in
the control panel and the connected manual call points, displays, etc.
Check the battery voltage:
Measure the voltage on the batteries. A voltage of > 24 V should be present.
Check the charging voltage:
Switch on / connect the mains (230 V) and reset the SHE system.
Wait until the control panel goes into standby mode.
Measure charging voltage in standby mode.
A voltage of > 26 V should be available.
Check quiescent current:
In order to ensure that the prescribed emergency power maintenance is
achieved over 72 hours, the quiescent current consumption of the SHEV con-
trol centre must also be measured.
must be connected in series with the disconnected charging circuit of the
batteries.
To obtain the correct quiescent current consumption, you must wait up to 5
minutes until the motor outputs are released.
A quiescent current < 55 mA should be measured.
Replace the emergency power accumulator after 4 years or if defects are
found (observe manufacturer's instructions).