Start-Up; Start Delay And Overrun Time; Maintenance; Cleaning - Maico ECA 100 ipro Montageanleitung Und Betriebsanleitung

Kleinraumventilator
Vorschau ausblenden Andere Handbücher für ECA 100 ipro:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

GB

8.4 Start-up

 Switch the mains fuse on.
 Carry out a function test.

8.5 Start delay and overrun time

When the setting button is pressed for
i
the first time, the value currently set is
displayed. The LEDs are off during
operation.
For condition in which unit is supplied,
i
see table in Chapter 3.1.
 Remove designer cover [7] carefully
(see Fig. B).
 Set start delay:
Press setting button [11] until the LED for
the start delay time you want lights up.
Wait until the LED flashes twice and goes
out. The value is now saved.
 Set overrun time:
Press setting button [12] until the LED for
the overrun time you want lights up. Wait
until the LED flashes twice and goes out.
The value is now saved.
When the setting buttons are
i
changed, the value currently set is
adopted.
 Fit designer cover [7] (see Fig. B).

9. Maintenance

The unit is maintenance-free.
18

10. Cleaning

Danger to life. Unit is
powered up.
 Switch the mains fuse off.
DANGER
Damage to unit if incorrect
NOTICE
cleaning agent is used!
 Only clean cover [6] and
designer cover [7] with water.
 Do not use aggressive
cleaning agents.
For ECA 100 ipro K: lamella may
NOTICE
break if cleaned incorrectly.
 Take care when cleaning. Do
not exercise force when
opening, shutting or bending
the lamella.
 Only clean inside parts of the fan with a dry
cloth.
 If the designer cover [7] is very dirty,
remove it carefully (see Fig. B) and clean
with water.
 Fit designer cover [7] (see Fig. B).

11. Fault rectification

● Call on the services of a trained electrician
any time there is a fault.
● Repairs should only be carried out by a
trained electrician.
Danger to life. Unit is
powered up.
 Switch off mains fuse before
DANGER
working on electrical
connection.
Fault
Cause / Measure
Fan does not
Start delay
switch on.
(max. 120 seconds).
Wait for the start delay
and reduce if necessary,
see Chapter 8.5.