Ip67-module
Vorschau ausblenden Andere Handbücher für BNI PNT-507-005-Z040:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5
Integration
5.1. Configuration
GSDML file
Integration of the
module
www.balluff.com
When planning Profibus devices, a device is depicted as a modular system with a header
module and several data modules. The screenshots shown here
have been taken from the configuration software of the Siemens HW config.
The device data required for project planning is saved in GSDML files (Generic Station
Description Markup Language). The GSDML files are available in two languages as an
Internet download (www.balluff.com). The data modules of an IO-Link block are depicted in
the project planning software according to the slot.
The GSDML file makes the possible data modules available (input or output of different
data ranges). For configuration of the IO-Link blocks, the corresponding data modules are
assigned to a slot.
The device can be found by searching in the catalog and inserted in the Profinet section by
drag & drop.
The BNIPNT507005Z040 / BNIPNT527005Z040 module with
submodules PN-IO, port 1-M12, port 2-M12 are used for
Profinet communication.
In X1 PN-IO, functions such as prioritized run-up or the domains for the ring topology can be
selected.
Slot 0 can be used for defining the port function (input, output, diagnostics input) or
diagnostics messages.
The remaining slots (2-5) preallocated in the default configuration are the placeholders for
the IO-Link modules or standard I/O modules. Slot 2 is for the first IO-Link port / standard
I/O port and Slot 5 for the last.
If IO-Link communication is planned for a given port, the standard I/O module must be
deleted and replaced with an IO-Link module, e.g., IOL_E_2byte.
12