Name
Settings
Logic gate
inactive
1 ... 2
1 ... 2: the selected number of logic gates with the associated parameters is
additionally available.
inactive: the logic gate output is not available.
Bluetooth
inactive
active
active: access to the sensor via Bluetooth is possible. The corresponding
parameters are available.
inactive: it is not possible to access the sensor via Bluetooth.
10.2
Light output 1..4
Name
Settings
Object light output
ON / OFF
Dimming level
Scenario
This parameter is used to select which object the output sends with.
0 % ... 100 %
ON level in percent
This parameter is used to select which dimming level to send for the ON
state.
OFF level in percent
0 % ... 100 %
This parameter is used to select which dimming level to send for the OFF
state.
Send switching object
ON / OFF
ON
OFF
This parameter is used to select whether to send the ON and OFF switching
commands for the dimming level object or whether to send only ON or only
OFF.
Switch ON scene
1 ... 64
This parameter is used to select which scene to send for the ON state.
Switch OFF scene
1 ... 64
This parameter is used to select which scene to send for the OFF state.
Send status cyclically
Do not send status cycli-
cally
ON / OFF
ON
OFF
This parameter is used for selecting whether the output not only sends after
any change but also cyclically and, if so, for which status.
Do not send status cyclically: no status is sent cyclically.
ON / OFF: ON and OFF status is sent cyclically
ON: only ON status is sent cyclically.
OFF: only OFF status is sent cyclically.
hh:mm:ss
Interval for sending cycli-
cally
Time interval for sending at cyclical intervals.
The maximum time interval is 18:12:15.
Light output mode
automatically ON and OFF
automatically OFF only
This parameter is used for selecting whether to switch the light output ON
and OFF automatically in relation to presence and light level (fully automatic
operation) or whether only to switch it OFF automatically (semi-automatic
operation).
Daytime operation
Yes
No
Setting to define whether light output is to be switched irrespective of light
level.
Internal
Light-level sensor ON
External
This parameter is used to define which light-level measurement the sensor
compares its switching threshold with.
10lux ... 1000lux
Initial level, light-level
sensor, external
This parameter is used to define which value the sensor works with until the
first value is received via the KNX bus.
KNX Application Description True Presence® KNX
Factory setting
Name
Weighting, light-level
inactive
sensor, external
This value defines the extent to which the external value is weighted.
Switching threshold ON
This parameter is used to select the ambient light threshold and level of
detected presence from which to switch the light output ON.
inactive
Switch OFF in relation to
light level
Yes: despite presence being detected, the light output is switched OFF if light
level is sufficient.
No: the light output stays switched ON until stay-ON time elapses. Stay-ON
time is re-triggered if presence is detected.
Light-level sensor OFF
Factory setting
ON / OFF
This parameter is used to define which light-level measurement the sensor
compares its switching threshold with.
Offset switching
threshold OFF
This parameter is used to select the offset from which to switch the light
100 %
output OFF.
Weighting, light-level
sensor, external
0 %
Stay-ON time, IQ mode
The stay-ON time automatically adjusts to the time persons spend in the
ON / OFF
detection zone.
Light output stay-ON
time
Stay-ON time is started if no presence is detected. This has the purpose of
preventing the output from switching OFF immediately if the room is only
vacated for a short time and having to be switched back ON again when a
1
person returns to the room.
Stay-ON time can be set from 00:00:10 to 18:12:15.
2
Disable output
This parameter is used for selecting whether the output can be disabled, and
which telegram can be used for disabling and re-enabling the output.
No: the output cannot be disabled.
Disabling with ON / enabling with OFF: the output is disabled by a telegram
with value "1" to the disabled object and enabled by a telegram with value
"0".
Disabling with OFF / enabling with ON: the output is disabled by a telegram
with value "0" to the disabled object and enabled by a telegram with value
"1".
00:00:30
Behaviour on disabling
This parameter is used to select whether to switch the output ON or OFF
automatically ON
before disabling or whether to leave the output unchanged.
and OFF
no action: no further action takes place before disabling.
ON: output is switched ON before disabling.
OFF: output is switched OFF before disabling.
Behaviour on enabling
NO
This parameter is used to select whether the output is to resume its activity
after enabling or whether to switch the output ON and OFF first.
Continue control: the output is immediately in normal mode and sets the
output in line with configuration.
Internal
ON: output is switched ON after enabling. Normal operation is reactivated
after a delay of 5 seconds.
OFF: output is switched OFF after enabling. Normal operation is reactivated
after a delay of 5 seconds.
Basic illumination
200
Setting to specify whether the basic illumination is to be activated.
- 32 -
Settings
Factory setting
1 % ... 100 %
100 %
10 ... 1000
500
Yes
Yes
No
Mixed light
Mixed light
External
(same object as ON)
10 ... 1000
100
1 % ... 100 %
100 %
Active
Active
Inactive
hh:mm:ss
00:05:00
No
No
ON for disabling /
OFF for enabling
OFF for disabling /
ON for enabling
no action
no action
ON
OFF
Continue control
Continue control
ON
OFF
inactive
inactive
active