Flexible pipe according to DN 125
Spiral ribbed pipe DN 125
Diagram 2: Value of the static pressure drop for selected pipes
Rectangular elbow horizontal 90°
Flexible tube (DN125)
Air intake grid
Total:
Table 3: Example of pressure drop calculation
Note: As mentioned above, the total loss of static pressure, which can be calculated by
adding up the losses of individual elements built into the pipeline system, may not exceed
95 Pa. If they do, the values of COP start dropping more dramatically.
DETERMINING THE FAN SETTING
When pressure drop is determined, select the mode in which the fan will operate. This
determines the speed of the fan. The mode is selected using Diagram no. 1, which shows
the aerodynamic characteristics of the fan depending on the air flow and pressure drop in
the pipeline*.
Note: *Pressure drop in the pipeline – in diagram 1 this is marked as pressure difference.
Zone of operation of the sanitary heat pump
On diagram 1 there are two zones of operation of the sanitary heat pump among the
curves:
• The dark zone represents the area of use with higher efficiency. The volumetric air flow
is higher in this zone, which requires a lower pressure drop (channel system version with
minimum pressure drop).
• The light zone represents the area of use with lower air flow in relation to the pressure
drop and fan setting.