9 Diagnostics and servicing
Code
Reason
Text mes-
sage
•
F264
Error during setup
Installation/
Setup error
•
F265
Sensor no longer carries out
a measurement
Measurement
function dis-
turbed
•
F267
Sensor cannot start
No executable
sensor soft-
ware
Function check
Code
Reason
Text mes-
sage
•
C700
A simulation is active
Simulation ac-
tive
Out of speci cation
Code
Reason
Text mes-
sage
•
S600
Temperature of the process-
ing electronics in the non-
Impermissi-
ble electronics
temperature
•
S601
Level echo in the close range
not available
•
S602
Compensation echo super-
imposed by medium
Level with-
in the search
range, com-
pensation
echo
52
Recti cation
•
Check for correct mounting
and/or parameter settings
•
Check probe length
•
Carry out a reset
•
Disconnect operating voltage
•
Exchanging the electronics
•
Send instrument for repair
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Recti cation
•
Finish simulation
•
Wait for the automatic end
after 60 mins.
The following table shows the error codes and text messages in the
status message "
causes as well as corrective measures.
Recti cation
•
Check ambient temperature
•
Insulate electronics
•
Use instrument with higher
temperature range
•
Reduce level
•
100 % adjustment: Increase
value
•
Check mounting socket
•
Remove possible interfering
signals in the close range
•
Use coaxial probe
•
100 % adjustment: Increase
value
DevSpec State in CMD 48
Bit 10 of Byte 0 ... 5
Bit 11 of Byte 0 ... 5
No communication possible
DevSpec
State in CMD 48
"Simulation Active" in "Stand-
" and provides information on
DevSpec State in CMD 48
Bit 8 of Byte 14 ... 24
Bit 9 of Byte 14 ... 24
Bit 10 of Byte 14 ... 24