Mounting and Installation
EN
7.3
Installation
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
12
SolConeX plug, 125 A
Series 8581/12
Explosion hazard due to insufficient protective measures!
Non-compliance results in severe or fatal injuries.
• Select suitable cables to ensure that the maximum permissible
conductor temperatures are not exceeded.
• When using core end sleeves, attach them using a suitable tool.
• Use only separately tested cable entries and stopping plugs with
an EU Type Examination Certificate.
• The conductor insulation must be touching the terminal.
• Do not damage the conductor (e.g. nicking) when stripping it.
• Always connect the protective conductor.
Explosion hazard in the case of installation in special areas with
potentially explosive dust!
Non-compliance results in severe or fatal injuries.
• Do not use the device in areas where there are processes
generating strong charges, machine friction processes,
separation processes and electrospray processes
(e.g. around electrostatic coating systems) and
pneumatically generated dust.
Explosion hazard when seal is insufficient and/or service temperature
is too high!
Non-compliance results in severe or fatal injuries.
• Only insert the plug if the pins and contact surfaces are free of
liquid and dirt.
• Completely seal the bayonet ring of the plug to obtain the degree
of protection.
• Make sure the service temperature range is maintained
(see the "Technical data" chapter).
DANGER
DANGER
DANGER
153705 / 8581605300
2020-08-27·BA00·III·en·07