Thermal power – kW
Thermal power – kW
FIRING RATES (A)
20157168
The burners can work in two ways: one-stage
and two-stage.
1st stage DELIVERY must not be lower than the
minimum limit in the diagram.
2nd stage DELIVERY must be selected within:
• Area A for applications in accordance with EN
This area provides the maximum delivery of the
burner in relation to the pressure in the combus-
tion chamber.
TEST BOILER (B)
The firing rates were set in relation to special test
boilers in accordance with the methods defined
in EN 267 standards.
20157169
Figure (B) indicates the diameter and length of
the test combustion chamber.
Example
Delivery 16 kg/hour:
diameter = 40 cm, length = 1 m.
Whenever the burner is operated in a much
smaller
chamber, a preliminary test should be per-
formed.
COMMERCIAL BOILERS (C) -
The burners are designed exclusively for com-
bustion chambers with flue gas outlet from the
bottom (for example three flue gas passes), ac-
cessible via the door.
Max thickness of the frontal boiler wall: 150 mm.
D814
D1863
7
267;
Important:
the FIRING RATE area values have
been obtained considering a surround-
ing temperature of 20 °C, and an atmos-
pheric pressure of 1000 mbar (approx.
100 m above sea level) and with the
combustion head adjusted as shown on
page 9.
commercially-available
combustion
Important