3) Automatic ON and OFF with presence detector (walking test for five minutes – see section 3.2.2.).
In this application, the presence detector does not react to light. The light sensor does not function.
- The lighting is automatically switched on when the presence detector detects motion within the detection range.
- The light is automatically switched off after a preset period if the presence detector detects no motion within the
detection range.
Optional: A push button can also be connected to manually switch the presence detector on and off.
4) Manual ON or OFF with push button or automatic OFF with presence detector (walking test for five
minutes – see section 3.2.2.).
For this application you should connect a push button (fig. 4.2).
In this application, the presence detector does not react to light. The light sensor does not function.
- The lighting is automatically switched off after a preset period if the presence detector detects no motion within
the detection range.
3.2. Settings
3.2.1. General
At delivery, the parameters are set as follows (factory settings):
sensitivity
application
light sensitivity
switch-off delay
LED motion indicator
The basic settings (sensitivity and application) can be changed using the DIP switches.
To set the sensitivity, use DIP switches 1 and 2. Figure 5 shows how to set these DIP switches for the desired sensitivity
of the light sensor (minimum, low, high, maximum).
Select the application using DIP switches 3 and 4 (see section 3.1.4.)
The IR remote control should be used to adjust all other settings. This is available separately.
3.2.2. Walking test
A walking test can be used to verify if the presence detector is operating correctly.
Select the walking test by setting the appropriate DIP switches (settings for application 3 or 4) or via the test button
(Test On/Off) on the IR remote control.
When the test is activated and the presence detector detects motion, the red LED indicator illuminates and the connected
lighting switches on for five seconds.
Attention:
• The walking test is not affected by daylight.
• Reset the DIP switches to their original position if daylight detection is used (application 1 or 2).
EN
high
application 1
100 lux
5 min
off (can only be changed using the remote control)
350-20056