Function (menu item)
User code
Limit Code
Prog. name
Version
Func. alt.
Lock time
Rel. Mode
Grad. Time
Namur
Range 1
Range 2
Range 3
Range 4
Contrast
Endress+Hauser
6.3.11
Operating parameter - PARAMETER/M55
In this menu item, configuration options such as the user code, failsafe mode of RIA452 to NAMUR
etc. can be configured.
Parameter setting
9999
Off
On
ILU00xA
V X.XX.XX
Time
Count
99.9
Off
On
1..100
No
Yes
3.6 (0.0 to 22.0)
3.8 (0.0 to 22.0)
20.5 (0.0 to 22.0)
21.0 (0.0 to 22.0)
0 to 99
Description
The option of editing the operating parameters is locked after entering a 4-digit
digital sequence (limit value code).
This lock is indicated on the display with the "key" symbol.
If the limit value code function is activated, only the configuration of the limit val-
ues is permitted. All other operating parameters cannot be modified.
Activation of restricted operation is indicated on the display with the "key" sym-
bol.
The item is only displayed if a user code was assigned.
Displays the name of the device software currently installed.
Version of the device software currently installed.
Setting for controlling pump rotation in alternating pump control.
• Time = switching time of the relay
• Count = switching frequency of the relay
Locking time of the relay, 0 to 99.9 s
Failsafe mode of the relays.
• Off = relays de-energize in the event of an error or device malfunction
• On = relays energize in the event of an error or device malfunction
Time setting for gradient evaluation, 1 to 100 s
Sensor evaluation to NAMUR (e.g. cable open circuit).
Only for 4 to 20 mA current signal.
Error limits for the input signal.
In the "NAMUR=Yes" operating mode, ranges 1 to 4 are assigned the limits spec-
ified by Namur NE 43 and cannot be changed.
In the "NAMUR=No" operating mode, the error limits can be freely selected.
Here, please note that the following applies: Range 1 < Range 2 < Range 3 <
Range 4.
Violation of these limits can be evaluated with a relay for example ("Alarm" oper-
ating mode).
Setting for the display contrast.
• 0 = low contrast
• 99 = high contrast
Commissioning
97