9 COMMISSIONING AND ADJUSTMENTS

Several user terminals may combined with the W3000+ controller:
W3000 compact LCD terminal (pGD1 display - 8 lines x 22 columns)
KIPlink (Keyboard in your Pocket, Wi-Fi interface).
The unit can only start if all the elements required for its start are ON.
If even just one control element is OFF, the unit remains off and indicates on the HMI (Human Machine Interface) which element is preventing the unit from
starting up.
If all the control elements apart from supervision are "ON", the unit remains off and the status of the unit is shown as: "OFF from supervision".
Below are the basic instructions for each of these devices. For further information read the W3000+ user and interface manual.
9.1

W3000 compact keyboard

[ALARM key]: displays the alarms and
resets normal operating conditions.
If it is on red, there is at least one
alarm/notification active.
[MENU key]: provides access to the
main menu. It turns yellow when inside
the menu.
[ESC key]: goes back one level in
the mask tree if you are in the header
masks, or returns to the unit controller.
Key combinations activate a set of specific functions
9.1.1

Switching the unit on and off

Using the ON/OFF parameter
The main mask displays the parameter "Com: On/Off'". "Off" means that the unit is switched off while "On" means that the unit is switched on.
Proceed as follows:
• Switching on: move to the "On/Off" parameter by pressing [ENTER] and then press [UP] or [DOWN] until "On" appears. Press [ENTER] again to
confirm. If "On" continues to be displayed it means that the unit has been switched on.
• Switching off: move to the "On/Off" parameter and change to "Off" using the same procedure used to switch the unit on. Press [ENTER] again to
confirm. If "Off" continues to be displayed it means that the unit has been switched off.
Installation, use and maintenance manual - Original instructions
Figure 9.1: keyboard representation.
• The back-lighting of the keypad turns off after 2 minutes when no buttons are pressed.
• The back-lighting of the keypad flashes when the unit is in alarm mode and there is no interaction with the keypad.
Key
[PRG + ALARM + UP keys]:
Increase screen contrast.
+
+
[PRG + ALARM + DOWN keys]:
Decrease screen contrast.
+
+
[ESC + ALARM keys]:
In the shared keyboard mode, this combination allows to share
screenshots and parameters among pLAN connected units.
+
[UP + DOWN + ENTER keys]:
press for 5 seconds to set the pLAN address on the user terminal.
+
+
[ALARM + UP keys]:
With the user terminal set to 0, it allows to configure the pLAN
address on the control board.
+
[UP key]: to move around the
masks and set the values of the
control parameters.
[ENTER key]: confirms entered
data.
[DOWN key]: moves around the
masks and sets control parameter
values.
NOTICE
Description
EN
117