Appendix A
DE
13
Appendix A
EN
FR
13.1 Technical Data
IT
Explosion protection
ES
Global (IECEx)
RU
Gas and dust
NL
DK
Europe (ATEX)
SE
Gas and dust
FI
PT
Certificates and approvals
GR
Certifications
PL
Technical data
CZ
Electrical data
SK
Rated operational
HU
voltage
Rated operational
SL
current
RO
Rated connection
BG
cross section
Ambient conditions
LV
Ambient temperature -60 to +100 °C (depending on the Ex components used)
LT
EE
Mechanical data
Degree of protection
CH
Material
KR
Enclosure
CN
Seal
Cover lock
Terminals
Mounting/installation
Connection
For further technical data, see r-stahl.com.
20
Control box, control and
distribution panels
Series 8146/5
IECEx PTB 06.0090
Ex db eb ia [ia Ga] ib [ib] mb op pr [op is Ga] q IIC T6, T5, T4, T3 Gb
Ex [ia Da] [ib] [op is Da] tb IIIC T80 °C, T95 °C, T130 °C, T135 °C Db
PTB 01 ATEX 1024
E II 2(1) G Ex db eb ia [ia Ga] ib [ib] mb op pr [op is Ga] q IIC T6, T5, T4, T3 Gb
E II 2(1) D Ex [ia Da] [ib] [op is Da] tb IIIC T80 °C, T95 °C, T130 °C, T135 °C Db
IECEx, ATEX
Max. 1100 V AC/DC
(depending on the terminal type and the Ex components used)
Max. 630 A
(depending on the terminal type and the Ex components used)
2
Max. 240 mm
(depending on the terminal type and the Ex components used)
(The storage temperature corresponds to the ambient temperature)
IP66 according to IEC/EN 60529
Polyester resin, glass fibre reinforced, dark grey, similar to RAL 7024
Impact strength ≥ 7 J
9
Surface resistance ≤ 10
Flame-resistant according to IEC/EN 60695, UL 94, ASTM D635
Standard: Foamed silicone
Special: Foamed PU (-20 to +80 °C)
with captive M6 stainless steel combo head screws
(Tightening torque: 4.5 Nm)
Tightening torque according to the specifications of the terminal block
manufacturers
Depending on the order, directly to the fitted components or to the terminal
blocks.
The rated operational voltage, the rated operational current and the rated
connection cross section depend on the terminal type and Ex components
used.
Ω
137193 / 8146620300
2023-03-23·BA00·III·en·10