11.5

Display modes

max
min
2
Fig. 37: Display test
11.5.1
Display status page
12.3
130
"Information": A menu element with information about the device status or settings that
cannot be changed.
"Selection/setting": A menu element that provides access to a changeable setting (ele-
ment with menu number <X.X.X.0>).
"Level up": A menu element with superordinate menu levels which you can switch to (e.g.
<4.1.0.0> in <4.0.0.0>).
Menu error page: In case of a fault, the current error number is displayed instead of a
status page.
Turn the operating button: Turn the operating button to increase or decrease settings or
menu numbers.
Press the operating button: Press the operating button to activate a menu element or
confirm a change.
Navigate: Follow the instructions below to navigate until the displayed menu number is
reached.
Wait time: The remaining time (in seconds) is displayed until the next state is reached au-
tomatically or a manual input can be made.
Set DIP switch to "OFF" position: Set DIP switch number "X" under the housing cover to
the "OFF" position.
Set DIP switch to "ON" position: Set DIP switch number "X" under the housing cover to
the "ON" position.
Display test
As soon as the electronic module has been supplied with power, a 2-second display test is
carried out. All characters of the display are shown. Then the status page appears.
After interruption of the power supply, the electronic module carries out various shut-off
functions. The display will be shown for as long as this process continues.
DANGER
Risk of fatal injury due to electrical current! Electrical charge
may still be present even if the display is switched off.
Coming into contact with live parts will result in death or serious injuries!
• Before working on the pump, disconnect the supply voltage and wait
for 5 minutes.
• Check whether all connections (including potential-free contacts) are
voltage-free.
• Never poke around in the openings on the electronic module and never
insert anything into it!
The standard view on the display is the status page. The current setpoint is displayed in the
number segments. Other settings are displayed using symbols.
NOTICE
For twin-head pump operation, the status page also indicates the operat-
ing mode ("Parallel operation" or "Main/Reserve") as a symbol. The partner
pump's display shows "SL".