AirConServiceCenter
Fault
The display shows
"Not enough UV. Add."
The display shows
"Not enough oil. Add."
The display shows
"Max. filling time
exceeded! Continue?
The display shows
"Ext. tank empty or closed
"
valve! Check!
The display shows
"Change the equipment
drier filter! Continue?
The display shows
"Change the vacuum
"
pump oil. Go on?
The display shows
"Printer not in line.
Carry on?"
The display shows
"Error 01"
EN
Cause
This message appears dur-
ing the filling process if there
is not enough UV additive in
the container to finish the
process.
This message appears dur-
ing the filling process if there
is not enough fresh oil in the
container to finish the pro-
cess.
This message appears dur-
ing the filling process if the
set amount of refrigerant
"
cannot be filled.
This message appears at
the start or during the filling
of the internal refrigerant
container if the set refrigerant
quantity cannot be attained.
This message appears
when you switch on the
AirConServiceCenter.
"
This message appears
when you switch on the
AirConServiceCenter.
This message indicates a
printer fault.
It was not possible to reduce
the pressure sufficiently
before the pressure increase
test.
Troubleshooting
Remedy
Fill the UV additive container.
ASC1000: make sure the
scales and container can
move freely.
Top up the fresh oil container
with a suitable oil type.
ASC1000: make sure the
scales and container can
move freely.
Check that
AirConServiceCenter con-
nections are not blocked.
Check if the external refriger-
ant container still contains
enough refrigerant or if the
valves of the external refrig-
erant container are open.
Change the internal filter
as soon as possible
(chapter "Changing dryer fil-
ter" on page 89). To proceed,
press Enter for 3 secs.
Change the vacuum pump
oil as soon as possible
(chapter "Changing the vac-
uum pump oil" on page 92).
To proceed, press Enter for 3
secs.
Check if there is paper in
the printer.
Check if the printer is
switched on (yellow LED
must light up constantly).
Check that the cover is
closed properly.
Check air conditioner and
connections for leaks, con-
strictions and ice build-up.
Check pressure transducer
calibration.