Functional
The Fronius Smart Meter records the current power at the feed-in point and transfers the
Description
data to the Datamanager. By controlling the Ohmpilot, the Datamanager adjusts any sur-
plus energy that is available to zero. In detail, this takes place by continuously adjusting
the heating element connected to the Ohmpilot.
This means that the surplus energy is used up by the heating element in a continuously
variable manner.
If no temperature sensor is fitted, an external source (e.g. gas-fired heating) must be
used to ensure the minimum temperature is met.
As an alternative, the Ohmpilot can also ensure the minimum temperature. For this, a
temperature sensor must be connected so that the Ohmpilot can measure the tempera-
ture. This may result in electricity being sourced from the grid.
The maximum temperature must be set on the heating element thermostat.
If the heating element does not have a thermostat, the Ohmpilot can also carry out this
task as an alternative (see "Optional Settings" section).
70
1
INPUT - grid supply 1x 230 V
Spring balancer 1.5 - 2.5 mm
NOTE! Phase and neutral con-
ductors must not be mixed up.
Residual current-operated circuit
breaker is triggered.
2
OUTPUT up to 3 kW variable, max.
13 A resistive load
Spring balancer 1.5 - 2.5 mm
3
Hot water boiler
4
PT1000 temperature sensor
5
External source (e.g. gas-fired
heating)
2
6
Heating element (max. 3 kW)
7
Residual-current circuit breaker
2
8
Circuit breaker max. B16A
9
Ferrite (included in delivery)