CAN bus cable connection
2.3.4
MASTER
Terminal resistor
2.3.5
The 120 Ω terminal resistor may only be installed in the last control component of a CAN bus cab-
le. The MASTER does not require a terminal resistor.
Connection of terminal resistor
2.3.6
120 Ω
Device 1
Note!
All SLAVE system controls and all CANBus-capable
hygiene flushing boxes are supplied with a 120 Ω
end resistor.
For non-terminal SLAVE or hygiene flushing box
system controls, the resistor must be removed!
© www.kemper-group.com – 01.2023 / K410068602008-00 – 103/265
Device 2
KHS Flush