IO-Link Master mit EtherCAT-Schnittstelle
11.1.1.5 Configuration area (0x8000 - 0x8FFF)
Index
Subindex
Name
0x8000
Port 1: Port Configuration
• 0x04
Device ID
• 0x05
Vendor ID
• 0x20
IO-Link Revision
• 0x22
Cycle Time
• 0x24
Process Data In Length
• 0x25
Process Data Out Length
• 0x28
Master Control
0x8008
Port 1: Vendor Specific Port Configuration
• 0x01
Validation ID
• 0x02
Reconfigure
• 0x03
Byte Swap
• 0x04
Mode UA
• 0x05
Current Limit UA
• 0x06
Current Limit US
Port 2: Port Configuration (Struktur: Ò Index 0x8000)
0x8010
Port 2: Vendor Specific Port Configuration (Struktur: Ò Index 0x8008)
0x8018
0x8020
Port 3: Port Configuration (Struktur: Ò Index 0x8000)
0x8028
Port 3: Vendor Specific Port Configuration (Struktur: Ò Index 0x8008)
0x8030
Port 4: Port Configuration (Struktur: Ò Index 0x8000)
Port 4: Vendor Specific Port Configuration (Struktur: Ò Index 0x8008)
0x8038
Mögliche Werte
0x000000...0xFFFFFF
0x0000...0xFFFF
• 0x10: IO-Link Revision 1.0
• 0x11: IO-Link Revision 1.1
• 0x00: Deactivated
• 0x01: Digital Input
• 0x02: Digital Output
• 0x03: IO-Link
• 0x00: No check
• 0x01: V1.0 Device, no Datastorage
• 0x02: V1.1 Device, no Datastorage
• 0x03: V1.1 Device, Backup + Restore
• 0x04: V1.1 Device, Restore
• 0x00: No action
• 0xFF: Activate configuration
• 0x00: No action
• 0x01: Byte swap
• 0x0000: UA = OFF - IO-Link Port Class A
• 0x0001: UA = ON - IO-Link Port Class B
(Default)
• 0x0002: Digital Output (DO)
• 0x0000: 0 mA
...
• 0x07D0: 2000 mA (Default)
• 0x0000: 0 mA
...
• 0x01C2: 450 mA
...
• 0x07D0: 2000 mA (Default)
AL1431
Datentyp /
Zugriff
UINT32 / rw
UINT32 / rw
UINT8 / rw
UINT32 / rw
UINT8 / rw
UINT8 / rw
UNIT16 / rw
UINT8 / rw
UINT8 / rw
UINT8 / rw
UINT16 / rw
UINT16 / rw
UINT16 / rw
55