Wiring diagram and Installation
All the communication of 485 cables between each module and terminal module to the central controller are
double core shielded twisted-pair cables. Specific wiring dimensions are mentioned in the table below:
The length of signal line
≤100
100<x≤200
200<x≤300
300<x≤400
400<x≤500
Installation conditions
• Do not install near devices that produce electrical interference such as AC motors, radio transmitters
like network routers and consumer electronics.
• Other electrical noise producers could include computers, auto-door openers, elevators, or other
equipment which can produce noise.
• Do not install in wet locations.
• It will cause failure if you install it in a place that shakes violently.
• Do not install in a place where it is exposed to direct sunlight or near to the heat. This will cause
failure.
Mounting Control
First, attach the mounting plate to the wall.
Using a job box is preferred. Use A and B
holes for a 86mm box, use C and D holes for
a 120mm box. Please take note of the UP
indicator.
Wiring dimension
2
0.3 mm
×2
2
0.5mm
×2
0.75mm
2
×2
2
1.25mm
×2
2
2mm
×2
A
51
C
B
D