Herunterladen Inhalt Inhalt Diese Seite drucken

BONFIGLIOLI Vectron Agile Schnellstartanleitung Seite 43

Vorschau ausblenden Andere Handbücher für Vectron Agile:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 56
Error messages and warnings during setup
Error messages
...
 
  
Warnings
...
  
  
     ,    
,
     
   
   
   
- Press ESC to correct a parameter value after an error message or after a warning message.
- Press ENT to ignore a warning message. Setup is continued. It is recommended to check
the entered data.
Error messages and warnings during operation
Error messages
,
   
,
 
...
 
 
...


,
 
...


...
          
    
...
         
 
  
  
  
05/2019
Fault clearance
Check rated motor values in parameters 370...376. Correct the values if neces-
sary. Repeat Setup. Check motor cable connections and frequency inverter con-
nections.
Check rated motor values in parameters. Correct the values if necessary. Repeat
Setup.
The following causes are possible: The motor cable cross-section is not sufficient.
The motor cable is too long. The motor cable is not connected correctly.
Check P372 (rated speed), P375 (rated frequency).
The machine data for star connection is entered, but the motor is connected in
delta. For star connection change the motor cable connection. For delta connec-
tion check the entered rated motor values. Repeat Setup.
The machine data for delta connection is entered, but the motor is connected in
star. For delta connection change the motor cable connection. For star connec-
tion check the entered rated motor values. Repeat Setup.
Check motor connection and frequency inverter connections.
Fault clearance
Frequency inverter overloaded. Check load behaviour. Check motor parameter
settings.
Overtemperature. Check cooling, fan, sensor and ambient temperature.
Low temperature. Check ambient temperature and electrical cabinet heating.
Motor temperature too high or sensor defective. Check connection on X.12.4.
Phase failure. Check motor and wiring.
Overloaded, short circuit or earth fault, motor current or phase failure. Check
load behaviour and ramps (P420 ... P423). Check motor and wiring.
DC link voltage too high or too low. Check deceleration ramps (P421, P423) and
the connected brake resistor. Check mains voltage.
Power failure or phase failure, voltage brake- chopper or motor chopper too
high.
Check mains voltage, mains fuses and circuit.
Electronic voltage (DC 24V) too high or too low. Check wiring of control termi-
nals.
Maximum frequency achieved. Check control signals and settings.
Check deceleration ramps P421, P423) and the connected brake resistor.
Internal STO-error.
Please use the instruction manual for details.
Enable signals STOA and STOB were not actuated at the same time, but with a
time offset bigger than 5 seconds. Check the circuitry of the enable input sig-
nals.
Internal STO-error.
Please use the instruction manual for details.
Minimum output current. Check motor and wiring.
Reference value signal on input X12.3 faulty, check signal.
Overcurrent on input X12.3, check signal.
Overcurrent on input X12.4, check signal.
43
Agile
Quick Start Guide

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis