11 Technical data

11.2.11 Current measurement I 3

Maschinenfabrik Reinhausen GmbH 2022
Interface
4
3
2
1
Table 53: Connector X2 (group 1)
Interface
4
3
2
1
Table 54: Connector X3 (group 2)
Interface
4
3
2
1
Table 55: Connector X4 (group 3)
Measurement
Nominal current I
N
Overload capability
Measuring accuracy
Rated frequency
Intrinsic consumption
Table 56: I 3 assembly technical data
8741483/00 EN
Pin
Description
4
Not used
3
V1- current input
2
V1+ current output
1
Not used
Pin
Description
4
Not used
3
V2- current input
2
V2+ current output
1
Not used
Pin
Description
4
Not used
3
V3- current input
2
V3+ current output
1
Not used
I 3
3-phase
0.5...6 A
1 A / 2 A / 5 A / 6 A
2 x I
N
Deviation < ±0.5% · I
N
50 / 60 / 16.7 Hz
< 0.1 W up to I = 1 A
< 0.3 W up to I = 5 A
®
TAPCON
250
101