Code
Range of
Default
displ.
variation
UG040 UG090
bb
(bC),...,199
163
bC
0,...,(bb)
43
bD
0,..., the lesser
25
between the value 50
and the value of P0
bF
1-199
3
Parameter zur Einstellung der seriellen Anschlüsse und
Fernbedienung
Cod.visual
Campo di variazione
C0
1,...,7
C1
0, ..., 4
C2
0, ..., 99
C3
0, ..., 199
C4
0, ..., 3
C5
0, .., 11
C6
0, ..., 199
C7
0, ..., 3
Code displ.
Range of variation
C0
1,...,7
C1
0, ..., 4
C2
0, ..., 99
C3
0, ..., 199
C4
0, ..., 3
C5
0, .., 11
C6
0, ..., 199
C7
0, ..., 3
Unit of measure
Description
175
giri/min/30
blower speed for rated production
(to be set according to the type of gas used ; see table 6.3.1.1)
51
giri/min/30
blower speed for minimum production
(to be set according to the type of gas used; see table 6.3.1.1)
25
%
minimum production % referred to rated production
(to be set according to the type of gas used; see Table 6.3.1.1)
days
inactivity days after which the complete discharge of the water contained in the boiler is
automatically performed
Default
Unità di misura
1
4
0
1
3
0
0
ms
0
Default
Unit of measure
1
4
0
1
3
0
0
ms
0
Parameters for setting the serial connection and remote control
Descrizione
Normalerweise angezeigter Wert
Aktivierung Tastatur und Fernbedienung.
Tastatur:
0= Ablesung aller Parameter
(Änderung nur von C1)
1= Ablesung und Änderung aller Parameter
2= Ablesung aller Parameter
(Änderung nur von C1)
3= Ablesung und Änderung aller Parameter
4= Ablesung und Änderung aller Parameter
Code für Aktivierung der Fernbedienung
Serielle Adresse
Baudrate
Frame
0=8,N,2 1=8,N,1 2=8,E,2
3=8,E,1 4=8,O,2 5=8,O,1
Verzögerung Übertragung der seriellen Antwort
Konfiguration des graphischen Displays
In den Fällen 1,2,3 wird bei Einschalten
die AUS-Regelung erzwungen
Description
Normally displayed value
Enable keypad and remote control.
Keypad:
0= reading of all parameters, (mod. C1)
1= reading and mod. of all parameters
2= reading of all parameters, (mod. C1)
3= reading and mod. of all parameters
4= reading and mod. of all parameters
Code for enabling remote control
Serial address
Baud-rate
Frame
0=8,N,2 1=8,N,1 2=8,E,2
3=8,E,1 4=8,O,2 5=8,O,1
Serial reply send delay
Graphic terminal configuration in cases
1,2,3 the OFF command is forced
on start-up
34
Tab. 8.3.2
1= Messung Raumfühler
2= Messung Zuluftfühler
3= Dampfproduktion
4= Stundenzähler
5= Leitfähigkeit
6= Wassertemperatur
7= Ventilatorgeschwindigkeit Brenner
Fernbedienung:
Ablesung und Änderung der Parameter P,
d und St
Ablesung und Änderung der Parameter P,
d und St
Ablesung der Parameter P, d und St
Ablesung der Parameter P, d und St
Ablesung und Änderung aller Parameter
0=1200 1=2400 2=4800 3=9600
(Bit pro Zeichen, Parität, Stoppbit)
6=7,N,2 7=7,N,1 8=7,E,2
9=7,E,1 10=7,O,2 11=7,O,1
0= Standarddisplay
1= Display mit EIN/AUS-Regelung
nicht verfügbar
nicht verfügbar
Tab. 8.3.3
1= Room probe measurement
2= Outlet probe measurement
3= Steam production
4= Hour counter
5= Conductivity
6= Water temperature
7= Burner fan speed
Remote control:
reading and modif. of param. P, d and St
reading and modif. of param. P, d and St
reading parameters P, d and St
eading parameters P, d and St
reading and modific. of all param.s
0=1200 1=2400 2=4800 3=9600
(character bits, parity, stop bits)
6=7,N,2 7=7,N,1 8=7,E,2
9=7,E,1 10=7,O,2 11=7,O,1
0=standard terminal
1=terminal with ON/OFF command
not available
not available
Tab. 8.3.3
cod. +030221931 rel. 5.0 - 05.11.2003