8.6 HEAT, COOL and DHW setpoint settings
SW6
SW1
SW3
SW4
SW2
SW7
SW5
NOTE
The
icon indicates which setpoint is being
modified
108
EN
DHW set point (min 30°C, max 60°C)
To change the DHW set point, proceed as follows:
•
press the SW1/SW2 buttons to select the set point
•
press the SW6/SW7 buttons to change the set point
•
confirm the modified value with the SW3 button
Single zone set point
Heat setpoint (min:max)
Type of terminal selected
FLH (radiant floor)
FCU (fancoil) / RAD (radiator)
(Cooling min 5°C, max 25°C - Heating min 25°C, max 65°C)
To change the single zone set point, proceed as follows:
•
press the SW1/SW2 buttons to select the set point
•
press the SW6/SW7 buttons to change the set point
•
confirm the modified value with the SW3 button
Zone Z1 set point
Heat setpoint (min:max)
Type of terminal selected
FLH (radiant floor)
FCU (fancoil) / RAD (radiator)
(Cooling min 5°C, max 25°C - Heating min 25°C, max 65°C)
To change the set point of zone Z1, proceed as follows:
•
press the SW1/SW2 buttons to select the set point
•
press the SW6/SW7 buttons to change the set point
•
confirm the modified value with the SW3 button
Set point zone Z2+
Heat setpoint (min:max)
Type of terminal selected
FLH (radiant floor)
FCU (fancoil) / RAD (radiator)
(Cooling min 5°C, max 25°C - Heating min 25°C, max 65°C)
To change the zone Z2 set point, proceed as follows:
•
press the SW1/SW2 buttons to select the set point
•
press the SW6/SW7 buttons to change the set point
•
confirm the modified value with the SW3 button
Cod. 3541V941 - Rev. 04 - 05/2022
Cool setpoint (min:max)
25: 55
18: 25
25: 65
5: 25
Cool setpoint (min:max)
25: 55
18: 25
25: 65
5: 25
Cool setpoint (min:max)
25: 55
18: 25
25: 65
5: 25
OMNIA S 3.2
Z1
Z2