Object
Description
Configuration of the static IP address if a DHCP server is not used. EtherNet/IP is not
IP Address
allowed to share the IP address with the CIM 500 webserver.
Subnet Mask
Configuration of the subnet mask if a DHCP server is not used.
Gateway
Configuration of the gateway address if a DHCP server is not used.
The CIM 500 module can be configured to automatically obtain its EtherNet/IP network
Use DHCP
settings from a DHCP server, if available on the network. Default: No use of DHCP.
For enabling a 5 seconds communication watchdog timer. Only active for pump or
booster products.
Communication
Unchecked: Watchdog is disabled (default).
Watchdog
Checked: Watchdog is enabled, time-out is 5 seconds.
Watchdog action: The pump or the booster is set to local mode.
The module can be put in product simulation mode to generate realistic simulated values
of all the EtherNet/IP input data. It is thus possible to connect an EtherNet/IP master to a
module fitted in a CIU or an E-box without installing this device in a real industrial process
system. In an office environment, it can then be verified that communication works, and
Grundfos product
data is received and handled correctly by the EtherNet/IP master application program (for
simulation
example PLC program) before installing the device.
To enable product simulation, select a product type from the dropdown list.
To terminate product simulation, select "No Simulation".
290