BNI EIP-508-105-Z067
Network interface
Construction and function
FE connection
LK1
EtherNet/IP Port 1
P
S
IN
Power supply input
BNIXXXX
US
UA
MOD NET
0
Port 0
00
1
Port 1
02
2
Port 2
04
3
Port 3
06
The Ethernet/IP-IO-Link master is a decentralized and
configurable gateway that processes and evaluates the
input and output signals of standard sensors and actuators
as well as process data from connected IO-Link devices.
The data is transmitted via an existing fieldbus interface to
00-19-31-XX-XX-XX
a higher-level controller set up by the user for further
LK1
processing.
A web server is available on the IO-Link master for
configuration and diagnostics.
The IO-Link master supports the Quick Connect function
IP
P
S
SN
for a quick (re)connection to the Ethernet network and the
GW
3
2
1
0
DLR protocol for redundant communication in a ring
topology.
IN
Display elements
POWER
BNIXXXX
BNI XXX-XXX-XXX-XXX
US
UA
MOD NET
100
LK1
100
LK2
0
00
01
08
1
Port/Pin LEDs
LED number
02
03
10
Even
2
Odd
04
05
12
3
06
07
14
2
english
Mounting hole
MAC-ID
00-19-31-XX-XX-XX
LK2
EtherNet/IP Port 2
IP
SN
GW
3
2
1
0
OUT
POWER
Power supply
output
BNI XXX-XXX-XXX-XXX
100
LK1
100
LK2
4
Port 4
01
08
09
5
Port 5
03
10
11
6
Port 6
05
12
13
7
Port 7
07
14
15
Mounting hole
MAC-ID
LK2
OUT
Status LEDs
4
Port/Pin LEDs:
09
Status of IO-Link und
5
I/O-Ports
Assignment
11
6
Pin 4
Pin 2
13
7
15
Display elements
Port/Pin LEDs Standard-Port
Display
Meaning
Off
State of input or output pins is 0
Yellow, static
State of input or output pins is 1
Both LEDs
Short circuit of sensor supply between
flashing red
pin 1 and pin 3
Red, static
Short circuit at output on pin 2/4 against
pin 3
Red, static
No high signal at diagnostic input
Red, static
24 V input signal on configured output
(actuator warning)
Port/Pin LEDs IO-Link-Port
Display
Meaning
Green, static
IO-Link connection active
Flashing
No IO-Link connection or incorrect
green
IO-Link device
Green, fast
IO-Link: Preoperate during data storage
flashing
Red, fast
Validation failed / incorrect configuration
flashing
of the IO-Link data length
Red, fast
Data storage failed / incorrect device for
flashing
data storage
Red, static
IO-Link: Short circuit of pin 4 against
pin 3
Status LEDs
LED
Signal
Meaning
US
Green, static
Input voltage OK
Red flashing
Input voltage low (< 18 V)
UA
Green, static
Output voltage OK
Red flashing
Output voltage low (< 18 V)
Red, static
No output voltage present
(< 11 V)
MOD Flashing
Incorrect or no module
green
configuration
Green, static
Module working
Red flashing
Fixed bus cycle not possible
Red/Green
Starting sequence
flashing
NET
Off
Module has no IP address
Flashing
Module has an IP address, but no
green
connection established
Green, static
Connection is established
Red flashing
Connection timeout
Red/Green
Starting sequence
flashing
100
Off
Transmission rate: 10 Mbit/s
Yellow, static
Transmission rate: 100 Mbit/s
LK1/2 Flashing
Data transfer
green