PEFY-P-VMM-A series
Item
Power source
Cooling capacity*1 / Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-Middle-High)
Fan
External static pressure*2
Noise level (Low-Middle-High)
Filter
Item
Power source
Cooling capacity*1 / Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-Middle-High)
Fan
External static pressure*2
Noise level (Low-Middle-High)
Filter
Item
Power source
Cooling capacity*1 / Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-High)
Fan
External static pressure*2
Noise level (Low-High)
Filter
PEFY-P-VMH-A series
Item
Power source
Cooling capacity*1 / Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-High)
Fan
External static
Pa
pressure*3
Noise level
dB(A)
(Low-High)
Filter
Item
Power source
Cooling capacity*1 / Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-High)
Fan
External static
Pa
pressure*3
Noise level
dB(A)
(Low-High)
Filter
Item
Power source
Cooling capacity*1 / Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate
Fan
External static
Pa
pressure*4
Noise level
dB(A)
Filter
Notes: *1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 27 °C DB/19 °C WB
Heating: Indoor: 20 °C DB
*2 The external static pressure is set to 50 Pa at factory shipment.
*3 The external static pressure is set to 100 Pa (at 220 V)/150 Pa (at 230, 240 V) at factory shipment.
*4 The external static pressure is set to 220 Pa (at 380 V)/260 Pa (at 400, 415 V) at factory shipment.
Model
P20VMM-A
kW
2.2/2.5
mm
295/815/700
kg
27
m
3
/min
6.0-7.2-8.5
Pa
30/50/100
dB(A)
27-30-32
Model
P63VMM-A
kW
7.1/8.0
mm
295/1,175/700
kg
42
m
3
/min
13.5-16.2-19.0
Pa
30/50/100
dB(A)
31-35-38
Model
P100VMM-A
kW
11.2/12.5
mm
325/1,415/740
kg
62
m
3
/min
23.0-33.0
Pa
50/130
dB(A)
40-44
Model
P40VMH-A
kW
4.5/5.0
mm
380/750/900
kg
44
3
m
/min
10.0-14.0
220 V
50/100/200
230, 240 V
100/150/200
220 V
27-34
230, 240 V
31-37
Model
P100VMH-A
kW
11.2/12.5
mm
380/1,200/900
kg
70
m
3
/min
26.5-38.0
220 V
50/100/200
230, 240 V
100/150/200
220 V
34-42
230, 240 V
38-44
Long life filter (option)
Model
P200VMH-A
3N~380-415V 50/60Hz
kW
22.4/25.0
mm
470/1,250/1,120
kg
100
m
3
/min
58.0
380V
110/220
400, 415V
130/260
380V
42
400, 415V
44
Long life filter (option)
Outdoor: 35 °C DB
Outdoor: 7 °C DB/6 °C WB
P25VMM-A
P32VMM-A
~220-240V 50Hz
2.8/3.2
3.6/4.0
295/815/700
295/815/700
27
27
6.0-7.2-8.5
7.5-9.0-10.5
30/50/100
30/50/100
27-30-32
28-32-35
Standard filter
P71VMM-A
P80VMM-A
~220-240V 50Hz
8.0/9.0
9.0/10.0
295/1,175/700
295/1,175/700
42
42
14.5-18.0-21.0
14.5-18.0-21.0
30/50/100
30/50/100
32-36-39
32-36-39
Standard filter
P125VMM-A
P140VMM-A
~220-240V 50Hz
14.0/16.0
16.0/18.0
325/1,415/740
325/1,715/740
65
70
28.0-40.0
29.5-42.0
50/130
50/130
42-45
42-45
Standard filter
P50VMH-A
P63VMH-A
~220-240V 50/60Hz
5.6/6.3
7.1/8.0
380/750/900
380/750/900
44
45
10.0-14.0
13.5-19.0
50/100/200
50/100/200
100/150/200
100/150/200
27-34
32-38
31-37
36-41
Long life filter (option)
P125VMH-A
P140VMH-A
~220-240V 50/60Hz
14.0/16.0
16.0/18.0
380/1,200/900
380/1,200/900
70
70
26.5-38.0
28.0-40.0
50/100/200
50/100/200
100/150/200
100/150/200
34-42
34-42
38-44
38-44
P250VMH-A
28.0/31.5
470/1,250/1,120
100
72.0
110/220
130/260
50
52
P40VMM-A
P50VMM-A
4.5/5.0
5.6/6.3
295/935/700
295/935/700
33
33
10.0-12.0-14.0
12.0-14.5-17.0
30/50/100
30/50/100
31-34-37
31-35-38
P71VMH-A
P80VMH-A
8.0/9.0
9.0/10.0
380/1,000/900
380/1,000/900
50
50
15.5-22.0
18.0-25.0
50/100/200
50/100/200
100/150/200
100/150/200
32-39
35-41
35-41
38-43
13

Werbung

Inhaltsverzeichnis