CAUTION
(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units
except any one of the outdoor units.
(When shipping: In shorted condition.)
For a system without link (no wiring connection between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-3)
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting. (Fig. 4-4)
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches that are less than 1 m are not included in the total branch number.) (Fig. 4-5)
(5) Use shielded wires for inter-unit control wiring (c) and ground the shield on both sides, otherwise misoperation from noise
may occur. (Fig. 4-6)
Connect wiring as shown in Section "4-3. Wiring System Diagrams".
(6) Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to CENELEC (HAR) rating
specifications) or use the cables based on IEC standard. (60245 IEC57, 60245 IEC66)
• Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 or 3 *1.5 mm
flexible cord. Type designation 60245 IEC 57 (H05RN-F, GP85PCP etc.) or heavier cord.
Downloaded from
www.Manualslib.com
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Outdoor unit
NO
Outdoor unit
Indoor unit
Branch
Point
Indoor unit
16 or fewer
more than 1 m
Indoor unit
less than 1 m
Indoor unit
manuals search engine
Outdoor unit
Prohibited
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Indoor unit
more than 1 m
Indoor unit
Shielded wire
Ground
Ground
11
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Branch point
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Fig. 4-3
Fig. 4-4
Fig. 4-5
Fig. 4-6