8. Diagnostics
This section includes the following topics:
8.1 Installation and operation troubleshooting
8.2 Errors indicated by the controller
8.1 Installation and operation troubleshooting
8.1.1 Skills
Manufacturer's personnel
COMPANY
Mechanical maintenance engineer
Electrical maintenance engineer
Operator
8.1.2 Safety warnings
If maintenance is required, follow the instructions and all indications in this manual and in the attachments. If
necessary, contact RIVACOLD srl assistance.
8.1.3 Causes and solutions
The packaged unit does not start-up
Cause
Power failure
The compressor's thermal
protection has tripped
The start capacitor is faulty
Instruction manual
v. 00 | 9600-0033
Rev.
BEST W R290
In case of maintenance, wear helmets, footwear and protective gloves.
Check the connection to the mains
l
Check that there is voltage on the electrical mains and that it
l
conforms to the rated data
Check the state of the circuit breakers on the machine
l
Check the integrity and activation state of the compressor
circuit breaker on the machine and, if present, the thermal
protection on the compressor
Replace the start capacitor.
© 2020 RIVACOLD srl
|
Solution
EN
129
131
Personnel
129