OPERATION

All manuals and user guides at all-guides.com
• Press the push-button control to open the valve.
• Automatic timed shut-off after ~30 seconds for showers (+5/-10 at 3 bar according to the European
standard EN-816) and ~7 seconds for urinals.
• Supply with cold water and hot water between 55-85°C (with a minimum temperature difference
of 50°C between the hot and cold water).
• The products are designed to withstand the thermal and chemical shocks as described by current
guidelines.
• Maximum supply pressure 10 bar (we recommend 1 to 5 bar dynamic pressure).
INSTALLATION
Do not remove the non-return valves integrated in the inlets in any circumstance.
THE INSTALLER MUST ENSURE:
• THE SEAL AROUND THE RECESSING HOUSING IS WATERPROOF TO PREVENT ANY INGRESS OF WATER;
• ANY WATER ACCIDENTALLY ENTERING THE RECESSING HOUSING (E.G. CONDENSATION, RUN
OFF, LEAKS, ETC.) HAS A DRAINAGE POINT TO PREVENT ANY STAGNATION;
• THE INTEGRITY OF THE SEALS BETWEEN THE STAINLESS STEEL WALL PLATE AND THE WALL
OR THE WALL PLATE AND THE MIXER/TAP/VALVE AT LEAST ONCE A YEAR, AND MAKE GOOD
IF NECESSARY.
If this advice is not followed, water may leak into the wall.
DELABIE cannot be held responsible for any ingress.
FOR FURTHER INFORMATION PLEASE CALL DELABIE TECHNICAL SUPPORT UK: 01491 821821.
ALL OTHER MARKETS: +33 (0)3 22 60 22 74.
• The flush tube supplied should be used with urinals without lids.
• For urinals with lids, the flush tube must be modified to ensure that the lid does not interfere
with the push-button control.
ADJUSTING THE FLOW RATE (fig. Q)
• The flow rate is pre-set at the factory at 12 lpm for showers (Refs fitted with ROUND shower heads are
set at 6 lpm) and 0,25 lps for urinals.
• The flow rate can be adjusted without shutting off the water or removing the mechanism.
• Remove the marker using circlip pliers. Adjust the flow rate on the push-button using a 3mm Allen key.
• Once the desired flow rate is achieved, replace the marker.
REMEMBER
• Our mixers/taps/valves must be installed by professional installers in accordance with current
regulations and recommendations in your country, and the specifications of the fluid engineer.
• Sizing the pipes correctly will avoid problems of flow rate, pressure loss and water hammer
(see calculation table in our brochure and online at www.delabie.com).
• Protect the installation with filters, water hammer absorbers and pressure reducers to reduce
the frequency of maintenance (recommended pressure from 1 to 5 bar maximum).
• Install stopcocks close to the mixer/tap/valve to facilitate maintenance.
• The pipework, stopcocks, bib taps and all sanitary fittings should be checked at least once a year,
and more frequently if necessary.
EN