BTS M30E0-_ _ _-H0001-S04G
Infrared Temperature Sensor
15
IO-Link Interface
15.9
Teach-In of Emissivity via IO-Link
The true object temperature that is lying within the detection range is written to the parameter True Temperature.
Sending the system command Teach Emissivity calculates the emissivity based on the previously entered true tem-
perature value and the measured temperature value with 100% emissivity.
Event
Measured
temperature
[°C]
500
True
Temperature
[°C]
500
Enter Object Temperature:
Entering the true temperature over the IO-Link-parameter True Temperature.
Note
The true temperature value must be entered in the units which have been set. If the temperature units are set
to %, then the true temperature value must be entered in °C.
Teach Emissivity:
Sending the system command Teach Emissivity teaches a new emissivity.
Note
The system command Teach Emissivity functions once after entering the true temperature value.
Note
If the calculated emissivity lies outside the valid range, the system command Teach Emissivity is acknowledged
with the error message function temporarily unavailable. The previous emissivity remains in effect.
15.10 Assigning BDC and Digital Outputs
Binary data channel
BDC1
BDC2
Note
The LED indicates whether the detected temperature lies above the set upper switching threshold.
Note
In IO-Link mode OUT2 is turned off (high-impedence).
www.balluff.com
All manuals and user guides at all-guides.com
Input
System command
True Temperature = 500
Teach Emissivity
Digital output (SIO mode)
OUT1 (Pin 4)
OUT2 (Pin 2)
t
New emissivity in effect
t
t
Status LED
LED OUT1 (yellow)
LED OUT2 (yellow)
english
41