Herunterladen Inhalt Inhalt Diese Seite drucken

BWT Multipur AP 65 Einbau- Und Bedienungsanleitung Seite 34

Rückspülfilter mit zeit- und differenzdruck-steuerung backwash filter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

EN
Technical Data
Multipur AP
Nominal connection width
Connection type
Flange Ø
Flangebore Ø
Nominal flow
Flow capacity at ∆p = 0,2 bar
Flow capacity at ∆p = 0,5 bar
Micron rating
Nominal pressure (PN)
Operating pressure p
Recommended operating pressure
Minimum pressure behind filter
(for backwashing)
Water temperature , min./max.
Ambient temperature, min./max.
Length of backwashing, approx.
Rinsing water volume at 4 bar
Water flow at backwashing
Mains connection
Operating voltage
Power consumption, max.
Power consumption during
backwashing, max.
CIC - dry contact, switching
capacity max.
Protection
Drainage connection, min.
Operating weight, approx.
Shipping weight, approx.
Product number (100 µm)
34
Type
DN
mm
mm
m
/h
3
m
/h
3
m
/h
3
µm
bar
min./max.
bar
o
bar
bar
°C
°C
s
l
l/h
V/Hz
V-
W
W
V / A
DN
kg
kg
PNR
125
125
Flange connection DIN 2501, Part 1
210
18
91
57
91
90/110
10
2,5 – 10
2,5 – 8
2,5
5 / 30
5 / 40
10
30
10000
230/50
24
8
12
24 V / 1 A (resistive load)
IP54
75
33
28
6-372041
150
150
240
22
105
61
105
38
32
6-372042

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis