System parameters
Parameters Description, values, default value
FOx
Function Output (switching function of the switching outputs 1/2)
1
Relay energises (transistor conductive) when the current value is below the switch point SPx
(= signalled state OUT1 "synchronous movement"; OUT2 "drive below preset value")
2
Relay de-energises (transistor blocked) when the current value is below the switch point SPx
(= error message OUT2 "drive speed too low"; for OUT1 not useful)
3
Relay energises (transistor conductive) when the current value is above the switch point SPx
(= signalled state OUT2 "drive speed reached"; for OUT1 not useful)
4
Relay de-energises (transistor blocked) when the current value is above the switch point SPx
(= error message OUT1 "slip"; OUT2 "drive speed exceeded")
5
Relay is energised (transistor conductive) within a frequency range (acceptable range)
6
Relay is de-energised (transistor output blocked) within a frequency range.
With functions 5 and 6 in connection with the parameter HYx (hysteresis)
a frequency range above and below the switch point SPx is defined.
Functions 5 and 6 are not useful for output 1 (FO1)!
• Values: 1...6
• Default value:
SOx
Store Output (latching function of switching outputs 1/2)
If the parameter is active, the outputs do not switch back automatically in case of a fault.
They must be reset internally or externally.
A reset is only possible in the Run mode. If the switching condition is maintained
after a reset the latching function becomes active again.
• Values: 0 = inactive / 1 = active front reset / 2 = front reset and external reset
• Default value: 0
FWx
Function Wire Monitoring (IN1/IN2, only FS-1N)
Relay characteristics for wire fault or short circuit, i.e. if input frequency = 0
Output 1 (slip/synchronous monitoring)
if
slip > switch point SPx
for switching functions 1 and 4
slip < switch point SPx
for switching functions 1 and 4
Output 2 (drive: frequency, rotational speed)
if
frequency > switch point SPx
for switching functions 1 and 4
for switching functions 2 and 3
frequency < switch point SPx
for switching functions 1 and 4
for switching functions 2 and 3
frequency in the window range
for switching function 5
for switching function 6
• Values: 0 = inactive / 1 = active
• Default value: 0
All manuals and user guides at all-guides.com
FO1 = 4 (output 1; error message "slip"; recommended)
FO2 = 2 (output 2; error message "drive speed too low")
FW1 = inactive (0)
relay de-energised
relay remains energised
FW2 = inactive (0)
relay energises
relay de-energises
relay remains energised
relay de-energised
relay de-energises
relay energises
FS-1 / FS-1N
MONITOR
FW1 = active (1)
relay remains de-energised
relay de-energises
FW2 = active (1)
relay remains de-energised
relay de-energises
relay de-energises
relay remains de-energised
relay de-energises
relay de-energises
29