06
Install the condensate drain. The device must be hung with a downward slant towards the condensate drain, to ensure that the conden-
sation water is drained quickly. (3cm/m)
The condensate drain system must be set up with an adequate p-trap in order to prevent the infiltration of odours. Always install a plug
for cleaning in the lower part of the p-trap in
order to allow quick disassembly.Pour water into the condensate collection pan and check if the liquid is drained properly. Otherwise,
check the inclination and look for possible blockages.
If the condensation drain pan is not used, the drain pipe must be connected directly to the condensati-
on trap. In this case, the hydraulic pipes and the valves used for cooling water must be insulated
against condensation
Position the drain pipes without mechanical stress on the drain connection of the unit.
07
Positon the casing and secure the screws at the top and bottom
of the device.
JAGA NV | BRIZA 12 - PLUG & PLAY | MANUAL | 2021.09.28 | V.3
08
Install the grille
EN
51