Fig. 5 :
Switching elements
and connections
Tab. 1
JP-1 and JP-2
(Fig. 5)
Configuration
Setting options on the escape door control terminal
F2
F1
A B
Arrangement diagram
Jumpers
Function
JP1
plugged
Pre-alarm switched on: An acoustic pre-alarm is triggered
in at
before an alarm. The pre-alarm does not affect the alarm
factory
contact or the visual display.
open
Pre-alarm switched off: An acoustic pre-alarm is suppressed.
After the time set on rotary switch S2 has elapsed, the alarm
is triggered.
JP2
plugged in
Permanent release switched on: Permanent release via the
at factory
key switch of the escape door control unit is possible.
open
Permanent release switched off: Permanent release via the
key pushbutton is not possible.
Jumpers (Tab. 1)
JP1
JP2
ON
S4
OFF
1 2 3 4 5
S3
Rotary switch S3 (Tab. 5)
S2
Rotary switch S2 (Tab. 4)
S1
Rotary switch S1 (Tab. 3)
C D E
DIP switch S4 (Tab. 2)
EN
EN
47