Type 9185/11-**-10
Hazardous area
The Fieldbus Isolating Repeater Type 9185/11-**-10 is an
associated apparatus as well as a nonincendive apparatus
for installation in Non-Hazardous, Class I, Division 2 or
Zone
2
Hazardous
(Classified)
intrinsically safe connections for one field device located in
Class I, II, III, Division 1, Group A-G or Class I, Zone 1 [AEx
ib] Group IIC, Hazardous Locations according to NEC
Article 504/505 as listed below.
Hazardous area:
Safe area:
Fieldbus Isolating Repeater Type 9185/1b-cd-10
b = numeral 1 or 2 for I.S. or non I.S. field interface
c = numeral 3 or 4 for type of field interface
d = numeral 5 or 6 for functionality
Entity parameters for wiring configurations are as follows:
V
OC
Type
[V]
[mA]
9185/11-35-10
3.73
9185/11-45-10
5.88
9185/11-46-10
5.88
Notes:
1.
Intrinsically safe apparatus may be switches, thermocouples, LEDs, RTDs or an FM Approved System or Entity
device connected in accordance with the manufacturer´s installation instructions.
2.
For Entity concept use the appropriate parameters to ensure the following:
V
or V
t
OC
I
or I
t
SC
3.
Electrical apparatus connected to an intrinsically safe system should not use or generate voltages > 250 V (U
4.
Installation should be in accordance with Article 504/505 of the National Electrical Code, ANSI/NFPA 70 and
ANSI/ISA RP 12.06.01.
5.
Installation in Canada should be in accordance with the Canadian Electrical Code, CSA C22.1, Part 1, Appendix F.
6.
Use a general purpose enclosure meeting the requirements of IEC 61010-1 for use in Non-Hazardous or Class I,
Division 2, Hazardous (Classified) Locations.
7.
Use an FM Approved Dust-ignition proof enclosure appropriate for environmental protection in Class II, Division 1,
Groups E, F and G; and Class III, Hazardous (Classified) Locations.
8.
These modules are to be mounted on DIN rail, DIN rail with pac-Bus (type 9194) or pac-Carrier (type 9195).
The field wiring in any case is connected to the ISpac device terminals.
9.
Ambient temperature:
WARNING:
Do not disconnect equipment when a flammable or combustable atmosphere is present.
AVERTISSEMENT:
Ne pas débrancher l'équipement en présence d'atmosphère inflammable ou combustible.
28.02.14
03
Reistle
Reistle
02
22.10.12
01
24.08.11
Reistle
Safe area
Locations
providing
Class I, II, III; DIV 1; Group A-G or Class I; Zone 1; Group IIC/IIB Hazardous Locations
Non-Hazardous; Division 2 or Zone 2 Hazardous (Classified) Locations
L
o
I
P
CL I, DIV 1, A,B/
SC
O
[mW]
Zone 1, GP IIC
149
139
1.3 mH
50
73.3
15 mH
50
73.3
15 mH
V
C
max
I
L
max
-20°C ... +70°C (any mounting position)
2007
04.05.
Einsiedler
F. Danko
Type 9185/12-4*-10
The Fieldbus Isolating Repeater Type 9185/12-4*-10 is a
nonincendive apparatus located in Non-Hazardous or Class
I, Division 2 or Zone 2 Hazardous Location.
L
C
o
o
CL I, DIV 1, C-G/
CL I, DIV 1, A,B/
Zone 1, GP IIB
Zone 1, GP IIC
7 mH
100 µF
56 mH
43 µF
56mH
43 µF
C
, C
+ C
o
a
i
leads
L
, L
+ L
o
a
i
leads
Fieldbus Isolating Repeater
Type 9185/1*-**-10
91 856 01 31 1
Safe area
C
o
CL I, DIV 1, C-G/
V
max
Zone 1, GP IIB
[V]
1000 µF
± 4.2
1000 µF
± 5.88
1000 µF
± 5.88
P
P
o
i
I
max
-
-
-
).
max
none
1 of 1