SHE Compact control panel EasyConnect 20A
12
Error messages / cause of fault
12.1
Error message on door display (yellow)
12.2
Status and error message on the 2 x 7-segment display of the motherboard
2 x 7-segment display for
error messages
56
Motherboard
in the housing door or on the SHE manual call point. The
Status message on the
2 x 7-segment display
OK
F.A
F A.
F.A.
F A = Activation SHE active (Fire-alarm)
Error message on the
2 x 7-segment display
E1
E2
E3 C1
or
E3 C2
E4 C1
or
E4 C2
E5 C1
or
E5 C2
E6
E8 C1
or
E8 C2
E14
Ready for operation
Mains failure
Battery fault
Fault in SHE manual call point
Fault in automatic detectors
Fault in monitoring
Drive line
Fault in connection to control panel
Fault in FAS
Meaning
Ready for operation
Channel 1 barred for
ventilation function
Channel 2 barred for
ventilation function
Channels 1 + 2 barred for
ventilation function
Cause of the
error message
Mains failure
Battery failure
Fault in line monitor
of SHE manual call point
channel 1 or channel 2
Fault in line monitor of auto-
matic detectors or automa-
tic detectors still active after
reset via CLOSE button
of SHE manual call point
channel 1 or channel 2
Fault in line monitor of
drive line
channel 1 or channel 2
Fault in connection to
control panel (bus)
alarm system (FAS)
channel 1 or channel 2
Ground fault
07/13424999424