5
Technical Data
Version
Gas explosion protection
Gas explosion protection
(IECEx)
Dust explosion protection
Dust explosion protection
(IECEx)
Certificates
IECEx certification
Rated cross section
Rated operational voltage U
Rated operational current I
Ingress Protection
Enclosure
Power dissipation and
temperature class
143457 / 826560300010
S-BA-8265-01-en-27/01/2009
Series 8265
E II 2G Ex d IIC T4 ... T6
8265/0: Ex d IIC
8265/4: Ex de ia/ib [ia/ib] IIC
8265/5: Ex de ia/ib [ia/ib] IIC T4 ... T6
E II 2 D Ex tD A21 IP 66 T*
* T
depends on the installed electrical equipment.
o
8265/0: Ex td A21 IP66 T*
8265/5: Ex td A21 IP66 T*
* T
depends on the installed electrical equipment.
o
8265/0: PTB 06 ATEX 1023 U
8265/4: PTB 06 ATEX 1076 U
8265/5: PTB 06 ATEX 1077
8265/0: IECEx PTB 07.0027 U
8265/4: IECEx PTB 07.0028 U
8265/5: IECEx PTB 07.0029
2
max. 95 mm
Standard:
max. 1100 V
e
Option
up to 10 kV
Enclosure
Current
e
Size 2
max. 160 A
Size 3
Size 4
Please refer to the individual type and rating plates of the devices!
II 2 G: min. IP 54
II 2 D: min. IP 66 (with additional O-ring)
aluminium, copper free (saltwater-proof)
8265/5 controller IEC:
Enclosure
for ambient temperature 40
T6
Size 2
30 W
Size 3
43 W
Size 4
62 W
for ambient temperature 55
T6
Size 2
18 W
Size 3
26 W
Size 4
35 W
8265/4 controller IEC, installed in Ex e enclosure:
Enclosure
for ambient temperature 40
T6
Size 2
27 W
Size 3
32 W
for ambient temperature 55
T6
Size 2
16 W
Size 3
19 W
o
C
T5
45 W
63 W
93 W
o
C
T5
30 W
43 W
62 W
o
C
T5
39 W
47 W
o
C
T5
27 W
32 W
Light-metal Ex d enclosures /